Introduction:
The ACVPP series hydraulic pressure regulator pilot valve is engineered for precise differential pressure control in refrigeration systems. Designed to maintain a constant pressure difference between the AM1 or AM3 main valves and the ACVPP reference pressure, ensuring optimal system performance.
Features:
Material: Carbon Steel
Temperature Range: -50°C to +120°C
Pressure Range: 0–10 bar
Mounting Options: Directly over AM1 or AM3 main valves; externally on CVH housing valves
Adjustment: Manual spindle for precise differential pressure setting
Standards Compliance: DIN, GB, ANSI
Applications:
Industrial refrigeration systems
HVAC systems
Ammonia and fluorine-based refrigeration circuits
High-temperature and high-pressure environments
Advantages:
Enhanced system stability and efficiency
Durable construction for extended service life
Easy integration with existing valve setups
Reliable performance across a wide temperature and pressure range
Characteristics:
– The Pilots ACVPP are used as differential pressure regulators, mounted directly over main valves AM1 or AM3. They can be also mounted on a housing valve
CVH in an external line to control one or more AM or RAK valves.
– The Pilots ACVPP working by differential pressure with a range of 0 Bars to 10 Bars.
– Turning the regulating spindle clockwise to increase the opening differential pressure of the pilot,(thus the evaporating pressure and temperature)and it
decreases when we turn the spindle anticlockwise.
– Pilot valve is used to keep the difference between AM inlet pressure and ACVPP reference pressure constant.